Dane techniczne
Model | Wyjście max. | Wyjście min. | Ciśnienie gazu gaz | Zasilacz | Silnik | Wielkość opakowania | waga | |||
KW | Kcal / h x 104 | KW | Kcal / h x 104 |
mbar |
V | KW | L x p x H mm | Kg | ||
M 17GRF | 168 | 14,5 | 69 | 6 |
20-200 |
230V / 50Hz | 0,15 |
580 x 460 x 340 |
15 | |
M 20GRF | 200 | 17,2 | 50 | 5 |
20-200 |
0.37 |
840 x 530 x 450 |
27 | ||
M 30GRF | 300 | 25,9 | 60 | 5.2 |
20-200 |
0.37 |
940 x 540 x 450 |
43 | ||
M 35GRF | 358 | 30,9 | 90 | 7.8 |
20-200 |
0.37 |
990 x 540 x 450 |
46 | ||
M 40GRF | 425 | 36,6 | 185 | 16 |
30-300 |
380V / 50Hz | 0.37 |
900 x 650 x 450 |
76 | |
M 60GRF | 738 | 63,6 | 248 | 21,4 |
30-300 |
1,1 |
1000 x 760 x 550 |
108 | ||
M 100GRF | 995 | 85,8 | 280 | 24 |
30-300 |
1,1 |
1000 x 760 x 550 |
110 | ||
M 120GRF | 1200 | 103,5 | 350 | 30 |
30-300 |
1.5 |
1050 x 850 x 580 |
120 | ||
M 150GRF | 1428 | 123 | 414 | 35,7 |
30-300 |
2.2 |
1150 x 850 x 650 |
144 | ||
M 200GRF | 2000 | 175 | 490 | 42 |
40-300 |
3.0 |
1400 x 1080 x 800 |
306 | ||
M 250GRF | 2500 | 220 | 590 | 50,9 |
40-300 |
7.5 |
1400 x 1080 x 800 |
310 | ||
M 300GRF | 2982 | 257 | 657 | 57 |
40-300 |
7.5 |
1500 x 1080 x 800 |
324 | ||
M 350GRF | 3500 | 300 | 924 | 80 |
40-300 |
7.5 |
1500 x 1080 x 800 |
330 | ||
M 400GRF | 3950 | 340 | 924 | 80 |
40-300 |
9.0 |
1500 x 1080 x 800 |
350 |
Jeden / dwustopniowy wykres krzywej
Całkowite wymiary
Model | ZA | b | do | re | mi | fa | L mm wielkości między otworów montażowych | Nφmm | M | NO. | |
szerokość mm | wysokość mm | długość mm | Długość rury palnika mm | średnica φmm Głowa | φmm Cylinderdiameter | ||||||
M 450GS / M | 962 | 740 | 1540 | 335 | 290 | 320 |
400 |
330 | M16 | 1 | |
M 550GS / M | 965 | 780 | 1660 | 399 | 350 | 380 |
480 |
390 | M16 | 1 | |
M 650GS / M | 1125 | 1075 | 1645 | 430 | 480 | 470 |
550 |
500 | M16 | 2 | |
M 1000GS / M | 1230 | 1094 | 1670 | 430 | 480 | 470 |
550 |
500 | M16 | 2 |
„N” oznacza rozmiar otworu w komorze.
Model | ZA | b | do | re | mi |
fa |
Rozmiar L mmThe między otworów montażowych | Nφmm | M | NO. | ||
Widthmm | Heightmm | Lengthmm | Długość tubemm wielkopiecowego |
φmmHead średnicy |
φmm cylindra średnicy |
minimum | max | |||||
M-3G | 245 | 270 | 410 | 50-105 | 90 |
90 |
130 | 155 | 95 | M8 |
1 |
|
M-6G | 245 | 271,5 | 410 | 50-105 | 90 |
90 |
130 | 155 | 100 | M8 |
1 |
|
M-11G | M 11TG | 245 | 271,5 | 475 | 90-150 | 108 |
90 |
130 | 155 | 120 | M8 |
1 |
M-17G | M 17TG | 350 | 350 | 650 | 80-200 | 108 |
95 |
130 | 155 | 120 | M8 |
2 |
M-20G | 475 | 365 | 740 | 120-280 | 135 |
114 |
170 | 206 | 140 | M10 |
3 |
|
M-30G | M 30TG | 475 | 365 | 835 | 170-300 | 135 |
135 |
200 | 244 | 145 | M12 |
3 |
M-35G | M 35TG | 475 | 365 | 925 | 130-350 | 155 |
135 |
200 | 244 | 165 | M12 |
3 |
M-40G | M 40TG | 470 | 397 | 1100 | 150-330 | 155 |
135 |
200 | 244 | 165 | M12 |
3 |
M-50G | 475 | 397 | 1150 | 150-350 | 155 |
135 |
200 | 244 | 165 | M12 |
3 |
|
* M-60G | * M 60TG | 560 | 485 | 1270 | 170-400 | 205 |
160 |
233 | 190 | M12 |
4 |
|
* M 100G | 560 | 485 | 1330 | 240-460 | 230 |
160 |
233 | 190 | M12 |
4 |
||
* M 100TG | 560 | 485 | 1330 | 220-440 | 270 | 195 | 276 | 220 | M16 |
4 |
||
* M 120G | 590 | 500 | 1400 | |||||||||
* M 150G | 655 | 587 | 1500 | 220-440 | 270 |
195 |
276 | 220 | M16 |
4 |
||
* M 150TG | 655 | 587 | 1500 | 300-600 | 320 | 220 | 339 | 240 | M16 |
4 |
||
* M 200G | 830 | 730 | 1850 | |||||||||
* M 250G | 875 | 730 | 1850 | 300-600 | 320 |
220 |
339 | 240 | M16 |
4 |
||
M 250TG | 875 | 730 | 1850 | 275-450 | 356 | 275 | 480 | 510 | 390 | M20 |
5 |
|
M 300G | 875 | 757 | 1850 | |||||||||
M 350G | 880 | 757 | 1850 | 275-450 | 356 |
275 |
480 | 510 | 390 | M20 |
5 |
|
M 400G | 880 | 760 | 1850 | 275-450 | 356 |
275 |
480 | 510 | 390 | M20 |
5 |
„N” oznacza rozmiar otworu w komorze.
Kiedy „E” jest większa niż „N”, oprócz bez FURANCE drzwi na tym kotle, należy otworzyć dziurę „N” większe niż „E” i potrzebują jednego ekstrawagancki kołnierz zainstalować palnik. Kontakt sprzedam biuro, jeśli potrzebujesz więcej szczegółów.